Analogue heating controller (AC 220 V) for flow temperature and boiler control (heat pump option). Direct replacement by digital unit RVP350, which has the same dimensions and/or panel cut-out. QAA32.2 room unit must be replaced (by QAA50.110/101), other sensors and valve actuator can be re-used. Info: Do not use the existing base as terminals are different - the Key data to replacement product: unit must be rewired (see Data Sheet).

Contact us!
We look forward to your inquiry, do not hesitate.
| Gewerbering 3 D-87480 Weitnau | ||
| Call: | +49 (8375) 9292092 | |
| Email: | shop@hvac.de | |
Copyright © 2017-2025 Stuhr GmbH