Reduced! RVP350 View larger

RVP350

Siemens

Heating controller for 1 heating circuit and d.h.w.

More details

S55370-C137

New product

Reduced from1 480,36 €
1 258,31 € *
(1 057,40 € VAT excl.)

Siemens RVP350

Weather-compensated flow temperature control of heating circuit with or without room influence, d.h.w. heating and demand based boiler temperature control.

Key functions
In addition to the functions of the RVP340, the RVP350 provides the following:
3 preprogrammed plant types can be selected, with automatic assignment of the functions required for each plant type

Weather-compensated flow temperature control through control of valve (mixing) in a heating circuit

Demand based control of the boiler temperature through control of the burner

D.h.w. heating with charging pump, electric immersion heater and solar collector


D.h.w. control
D.h.w. control independent of the heating circuit. Control can be enabled as follows:
According to its own 7-day program

According to the program of the heating circuit

According to the programs of the zone controllers on the data bus

Permanently (24 hours a day)


D.h.w. heating features a legionella function, which can be deactivated. Legionella protection is activated once a week. The d.h.w. temperature is acquired with sensors or thermostats.

Boiler temperature control
Boiler temperature control operates as demand-dependent 2-position control. The boiler temperature is controlled through cycling of a 1- or a 2-stage burner (direct burner control). When there is no heat request, the boiler will either be shut down or maintained at the minimum temperature (selectable). Both minimum and maximum limitation of the boiler temperature are adjustable.

Viewed products

2 other products in same category

Product successfully added to the product comparison!