OSC20 Optimizer with ONLY a room sensor. Replacement RVL480 is a compensator / optimiser with additional functions, and the same dimensions. The existing room sensor can be re-used however a QAC22 outside sensor is required. If no control of the flow temperature is needed, the flow temperature sensor can be simulated by a fixed 1300 ohm resistor (63°C) across terminals B1 and M.